Technical Specifications
|
|
Input :
|
Thermocouple / RTD sensor
|
|
Resolution :
|
10C Standard 0.10C
optional
|
|
Sensor break protection :
|
Built-in, relay OFF and display reads
1
|
|
Accuracy
Set point :
|
Absolute
|
|
Control Mode :
|
ON/OFF with standard 10C
hysteresis Or Time proportioning with standard +
100C Bandwidth and 20 seconds cycle time
centred around
set point.
|
|
Control Output :
|
Standard 5Amp, 230V AC SPDT mechanical
relay.
|
|
Cold junction compensation :
|
Automatic
|
|
Indication &
Control drift :
|
<0.30C, constant after
18 hours (Test condition-Ambient @ 450C,
Cr/AI thermocouple for worst case)
|
|
Control response time :
|
20 milli seconds standard
|
|
Indication response
time :
|
200 milli seconds typical
|
|
Common mode rejection :
|
90dB@50Hz
|
|
Input filter cutoff :
|
10KHz
|
|
Display :
|
Easy-to-read 12.5mm high 7 segement
LED display Or 1 inch high 7-segment LED display in
96H x 96W mm instrument
|
|
Operating temperature :
|
50C to 550C
|
|
Input power :
|
230V Ac, + 20% @ 50Hz
|
|
Dimensions :
|
96H x 96W x 110D mm
74H x 74W x 110D mm
|
| |
|